Model Number: MOD 20K~80K/100K~160KVA (3:3)
Brand Name: AWP
Key Specifications/Special Features:
Modular 20 series UPS is redundant, scalable, 3-phase UPS power protection system with on-line double-conversion and full DSP control technology and highly enhanced output power factor to 1.0, hot-swappable and flexible power module configuration makes capacity scalable from 20/20kW up to 160/160kW and system capacity can be expanded to 320/320kW by advanced N + X wireless parallel and redundancy technology, all internal modules (monitoring module, power module and charging module) are modularly designed and hot-swappable, assuring system compactness, reliability and easy maintenance, modular 20 series UPS was specifically designed to ensure maximum protection of mission critical data center or critical applications loadsHighlights:Hot-swappable modularityEasy expandability and scalabilityHigh power densityHigh output power factor (PF1.0)Integrated power distribution
Dual-mains input
Small footprint
Model | MOD 80 | MOD 160 | ||
Capacity | 20-80kVA 20-80KW |
20-160kVA 20-160kW |
||
Numbers of parallel module | 1-4 | 1-8 | ||
Numbers of redundancy module | 0-3 | 0-7 | ||
Rated capacity of each power module | 20kVA/20kW | |||
Input: | ||||
Rated voltage | 380/400/415V AC | |||
Voltage range | 204-242 V AC (load ≤ 50%) 242-277V AC (50% < load ≤ 70%) 277-520V AC (70% < load ≤ 100%) |
|||
Rated frequency | 50/60Hz (auto-sense) | |||
Frequency range | 40-70Hz | |||
Power factor | ≥ 0.99 | |||
Bypass voltage range | ≤ 3% | |||
Delayed start of rectifier | rated output voltage: - 40%- + 20% (settable via LCD) | |||
Output | ||||
Voltage | 380/400/415V AC | |||
Voltage regulation | ± 1% | |||
Frequency | battery mode: 50/60Hz ± 0.1% mains mode: synchronized with utility frequency conversion mode: 50Hz input and 60Hz output or 60Hz input and 50Hz output |
|||
Waveform | sinusoidal | |||
Power factor | 0.9 | |||
Crest factor | 3:1 | |||
Total harmonic distortion (THDV) | ≤ 2% (linear load) ≤ 5% (non-linear load) |
|||
Transfer time | AC mode to battery mode: 0 minute inverter mode to bypass mode: 0 minute inverter mode to eco-friendly mode: 5-10 minutes |
|||
Inverter overload capability | 105%: longtime running 105-110%: transfer to bypass in 1H 110-125%: transfer to bypass in 10 minutes 125-150%: transfer to bypass in 1 minute 150-200%: transfer to bypass in 200 minutes > 200%: transfer to bypass in 100 ms |
|||
Slight adjustment of inverter output voltage | ± 5V | |||
Batteries | ||||
DC voltage | ± 240V DC (± 192 / ± 204 / ± 216 / ± 228V DC selectable) | |||
Inbuilt battery of standard model | 12V/9Ah x 40 for each module | |||
Charging current | 1-30/60 A (settable via LCD) | |||
System | ||||
Efficiency | ≥94% | |||
Display panel | 5.7 inches LCD touchscreen | |||
Protections | short-circuit, overload, over-temperature, overvoltage, under voltage, IGBT pulse -by pulsecurrent limiting, early warning of battery low voltage and battery overcharge protections | |||
Alarm | battery mode, low battery, fans fault | |||
EMI | EN62040-2 | |||
EMS | IEC61000-4-2 (ESD) IEC61000-4-3 (RS) IEC61000-4-4 (EFT) IEC61000-4-5 (Surge) |
|||
Communications | ||||
RS232/RS485/USB/dry contacts (standard) | supports Windows 98/2000/2003/XP/Vista/2008/7/8/10 | |||
SNMP (option) | power management from SNMP manager and web browser | |||
Others | ||||
Humidity | 0-95% RH at 0-40℃ (non-condensing) | |||
Noise level | ≤ 60dB | |||
Module dimensions | (W) 482 x (D) 590 x (H) 590mm | |||
Module weight | 28kg/power module, 27 kg / charger module, 7kg /monitoring module | |||
UPS dimensions | (W) 600 x (D) 1000 x (H) 1600mm | (W) 600 x (D) 1000 x (H) 2000mm | ||
UPS packing | (W) 700 x (D) 1070 x (H) 1070mm | (W) 700 x (D) 1070 x (H) 2060mm | ||
UPS weight Without inbuilt battery and power module |
Net weight: 225kg Gross weight: 245kg |
Net weight: 290kg Gross weight: 310kg |
||
Input /output/bypass breaker | Yes | Yes | ||